How Many Amps Does a Sump Pump Use?

A sump pump at 800W and 120V draws 6.67 amps.

Sump Pump Amps Explained

A standard 1/3 HP to 1/2 HP sump pump draws around 800 watts at 120V, which is 6.67 amps, plugged into a standard dedicated outlet in the basement or crawlspace. Because a sump pump activates suddenly via a float switch and must never lose power during a storm, NEC recommends its own dedicated circuit not shared with a sump pump backup battery system, freezer, or other critical equipment, and many homeowners add a battery backup or water-powered backup pump for outages.

Frequently Asked Questions

How do I convert watts to amps?

For DC circuits, divide watts by volts (Amps = Watts ÷ Volts). For AC single-phase circuits, divide watts by the product of power factor and volts. For AC three-phase circuits, divide watts by the product of √3, power factor, and volts.

Why do I need power factor for AC calculations?

Power factor accounts for the phase difference between voltage and current caused by inductive loads like motors and compressors. Purely resistive loads (heaters, incandescent bulbs) have a power factor of 1.0. Motors typically run 0.8–0.95.

What breaker size do I need for a 1500W appliance at 120V?

1500W at 120V draws 12.50 amps. Per NEC Article 210.20, continuous loads must not exceed 80% of a breaker rated capacity, so a 15A breaker (12A max continuous) is not sufficient. A dedicated 20A circuit is required.

Does this calculator work for 240V appliances?

Yes. Enter your wattage and set voltage to 240V for dryers, water heaters, ranges, and EV chargers. At the same wattage, 240V circuits draw half the current of 120V circuits.

Is this calculator accurate for 3-phase industrial power?

Yes. Select the AC 3-Phase tab, enter your line voltage (commonly 208V or 480V), and choose line-to-line or line-to-neutral mode. The calculator uses the precise value of √3, not a rounded 1.732 approximation.

Can I use this to size wire gauge?

The calculator provides an AWG wire gauge recommendation based on NEC Table 310.15(B)(16) for 60°C copper conductors. Always confirm final wire and breaker sizing with a licensed electrician before installation.